Trouble Shooting:
1. Check the local temperature, the altitude of the area, whether the pool has insulation measures?
2. Ask about the actual capacity of the pool, is the surface area of the pool too large?
3. Pump flow rate size
4. Is the actual running time of the equipment long enough?
5. Connecting pipeline is too long, generally recommended that the total length of the pipeline should not exceed 10-15 meters.
Fault Resolution:
1. The surface area of the pool is too large, the temperature difference between day and night is large, need to add the insulation cover, (elevation areas will lead to equipment heat loss)
2. Pool capacity is too large, need to drain part of the water, it is best to ensure that the 4000 gallons or less.
3. For this equipment, the reasonable operating range of the water pump flow is 600GPH to 1000GPH. (If the water pump flow rate is too fast, install a valve at the water pump inlet to reduce the flow rate)
4. If you set the timing or running time is not long enough, the first heating time needs to be heated for at least 48 hours to 72 hours, you need to ensure that the equipment is not disconnected, do not turn off the machine to observe the warming situation.
5. Shorten the distance between each device to reduce heat loss.